UPS battery and battery care
With the right environment and UPS battery care, you get longer battery life
UPS technology & systems
UPS battery maintenance and care
The batteries in a UPS system play a crucial role and are just as important as the UPS itself. At the same time, batteries are the system's greatest vulnerability, making it all the more important to look after them carefully. They also have a major impact on both installation costs and running costs.
As the battery life comes to an end, the internal resistance gradually increases. Eventually, it reaches a critical level, clearly signalling that it is time to replace the battery. To facilitate the process, we offer easy ordering of new batteries directly from us. We make sure to deliver quickly and safely so that you avoid unnecessary interruptions in operation.
To take care of your old batteries, we also offer a convenient service where we take care of both the destruction and the recycling. In this way, we help you not only to replace them but also to contribute to a more sustainable environment.
Factors affecting the UPS battery
Poor battery quality, unfavourable temperature conditions, lack of monitoring and frequent discharges cause batteries to be replaced prematurely.
UPS battery - extend battery life
By creating optimal conditions for storage, you will significantly extend the life of your batteries. Good ventilation, together with temperatures in the range of 20-22 degrees, creates an environment that favours battery durability. To further ensure high performance, you should regularly monitor the internal health of your batteries.
By using a battery monitoring system, you can easily keep track of important parameters such as temperature, volts and resistance. This allows you to quickly identify batteries that are starting to underperform. You can then replace them in time and avoid them negatively affecting the other batteries in the system.
UPS battery - things to consider
- Ambient temperature around 20-22 degrees
- Battery quality from the factory
- Regular check of resistance and voltage
- Battery monitoring system
- Order batteries and monitoring from us
Eurotech offers the right conditions for the right UPS battery
BAcs for battery care
Battery Management System (BMS)
Eurotech is a fully certified reseller of BACS, the leading battery care system from the German company Generex. BACS extends the life of batteries and has a positive impact on the investment calculation over an extended period of time.
How does BACS battery monitoring work?
BACS performs an analysis of each individual battery block in a loop, allowing early detection and replacement of defective batteries before they affect others. Each battery block has a mounted module where the terminal voltage is measured and monitored through software. You integrate BACS with existing UPS systems and include it as standard in new installations.
Benefits of BACS battery monitoring
- Cost-effective battery care system
- Increases reliability of UPS systems
- Saves costs and time
- Can increase battery life
You can find BACS under other accessories
Other accessories
Bypass peripherals, monitoring systems and communications.
Regulation of the European Parliament and of the Council on
UPS Battery and spent batteries
Demand for batteries is increasing rapidly and could rise up to 19 times in the coming years. This exponential growth clearly demonstrates the increasing strategic importance of the battery market, especially in industrial and stationary applications. At the same time, researchers and engineers are rapidly advancing battery technology and paving the way for solutions that meet these growing demands.
In order to create a sustainable and long-term positive impact, actors across the EU market need to implement a harmonised regulation for the battery cycle. This regulation will ensure that companies produce and manage spent batteries responsibly and contribute to a circular economy.
The proposal can be divided into three different parts:
- The part before the battery is put into service
Producer responsibility is increasing to specify the amount of different metals and the proportion of recycled materials in batteries. It is also accompanied by increased information and labelling requirements to help the market assess the performance and life expectancy of batteries.
- The part when the battery is in use
Battery management systems need to fulfil requirements to effectively assess the lifetime and remaining capacity of batteries. Thus, because it is a key element and because the requirement means that batteries can extend their lifetime, as well as be given a second chance by being used in new applications when they have reached their original lifetime. For example, in UPS systems. Therefore, the possibility of using batteries in later stages for energy storage systems when they have served their purpose in their primary applications is emphasised.
- The part when the battery can no longer be used
To this end, the EU is setting recycling targets for different types of batteries and strengthening producers' responsibility for recycling. The European Commission presented a proposal for a new regulatory framework on 10 December 2020. The European Parliament has examined the proposal and proposed various amendments. The next step is for the Commission to consider these amendments and present a final version of the proposal.
As part of the new regulatory framework, the EU requires by 1 January 2026 that rechargeable industrial and traction batteries include a battery management system.
There is uncertainty about which batteries are covered by the battery management system proposal. Previously, legislators set a limit of 2 kW/h, but Parliament chose not to include that part. In addition, the proposal excludes batteries weighing less than 5kg, which means that UPSs with internal batteries of 7 Ah to 12 Ah are exempt from the requirement. Article 14, Chapter III, specifies the role of a battery management system and is of particular relevance.
The legislative documentation defines a ”battery management system” as an electronic component that monitors and controls the electrical and thermal functions of the battery. The system manages and stores data on battery parameters to assess ageing and life expectancy, and communicates with the device where the battery is installed. The EU Council establishes that a ”battery management system” must fulfil data measurement requirements according to a framework of key parameters.
Battery management system
Necessary data measurement
According to the EU Council, a ”battery management system” is required to actively meet or provide the necessary data measurement according to a framework of key parameters. These parameters and their link to the GENEREX BACS product family are described in more detail below.
Battery capacity
1. remaining capacity - BACS
Starting in 2022, BACS will enable real-time calculation and display of individual cell and battery capacity. To provide a better understanding of BACS functionality, below are some key parameters that BACS monitors and presents:
Residual Battery Efficiency (Round Trip Efficiency):
The efficiency is calculated by a direct comparison between two distinct discharges. Furthermore, the BACSVIEWER REPORT function shows the difference between these two discharges and represents the efficiency. However, the efficiency decreases with age and number of discharges, which BACS accurately tracks.
Battery capacity:
The AC/DC resistance is plotted against the available capacity of the cell, expressed as a percentage of nominal capacity. In addition, BACS is the only BMS on the market that presents battery capacity together with AC/DC resistance. This also includes parameters such as battery current and temperature in the capacity measurements, giving a more complete picture of the battery condition.
Total loss of capacity:
The capacity loss is calculated by comparing the difference between the nominal capacity of the battery when new and the result of a recent discharge test. Moreover, the BACSVIEWER software makes the comparison simple and accessible, facilitating users' analysis work.
Remaining Power Capacity and Power Loss:
The power is determined by comparing the ”Battery Capacity” of the cell with the first recorded discharge at start-up. Furthermore, BACS ensures that each battery reaches 100 % states of charge, allowing comparability of discharge tests. By utilising the long-term data from BACSVIEWER, users can quickly determine the lifetime power loss.
Autonomy time:
BACS also provides an autonomy time calculation based on UPS input, battery current, battery voltage, temperature and impedance. This makes it easy to get a clear estimate of how long the battery can keep the system running during operation.
Determination of Battery Capacity by Discharge Tests:
To accurately determine the available capacity, the battery must be discharged. BACS measures capacity once per second during discharge, enabling risk-free testing without unnoticed damage to cells or batteries. In addition, BACS offers comprehensive monitoring and accurate analysis of battery parameters. This provides users with insights into performance, efficiency and life expectancy, while minimising the risk of system disruption during online discharge tests.
Impedance
Ohmic resistance and/or electrochemical impedance
In short, BACS indicates this through the ”RI” reading; the trend line in the BACS VIEWER shows life expectancy.
Resistance
AC/DC resistance or conductance monitors the health of a cell and follows its ageing profile. However, AC/DC resistance or conductance monitoring cannot accurately determine when a product reaches a specific capacity value, such as 80 % of nominal. Instead, it effectively identifies faulty cells before they cause battery problems.
By plotting AC/DC resistance values against time, you create a broad ageing profile for cells or batteries in operation. With this method, you can predict when cells need to be replaced. In addition, AC/DC resistance monitoring builds a life profile by tracking changes in AC/DC resistance or conductance over time as a cell ages.
Always measure AC/DC resistance on fully charged cells to get reliable results. In high voltage string applications such as UPS, cells or blocks often lead to deviations from the ideal float charge voltage, with differences of 2V or more within the string. BACS eliminates these voltage differences and ensures that all cells and batteries remain equal, with no more than 0.01V difference between neighbouring cells or batteries. This balancing system allows you to reliably compare AC/DC resistance values and use the measurements for diagnostic purposes.
Baseline RI
If the test is initial, BACS stores the AC/DC resistance or conductance as the initial AC/DC resistance for later comparison as the battery ages. In addition, BACS offers configurable threshold settings for RI resistance based on absolute values in mOhm. It can be dynamic or based on a given set of ”Base Line” values, depending on the needs of the installation.
Battery capacity
1. remaining capacity - BACS
Since 2022, BACS calculates and displays in real time the individual capacity of cells and batteries. To provide a better understanding of BACS functionality, we list below some key parameters that the system monitors and presents:
Residual Battery Efficiency (Round Trip Efficiency):
BACS calculates the efficiency by directly comparing two distinct discharges. Then, the BACSVIEWER REPORT function shows the differences between these two discharges and represents the efficiency clearly. The system also accurately tracks how efficiency decreases with battery age and number of discharges.
Battery capacity:
BACS plots the AC/DC resistance against the available capacity of the cell, expressed as a percentage of its nominal capacity. In addition, BACS is the only BMS on the market that simultaneously presents battery capacity along with AC/DC resistance, battery current and temperature. This combined information provides a more complete picture of battery condition and performance.
Total loss of capacity:
BACS calculates the capacity loss by comparing the difference between the nominal capacity of the battery when new and the result of a recent discharge test. Furthermore, the BACSVIEWER software facilitates this analysis and makes the comparisons simple and accessible to the user, thus streamlining the analysis work.
Remaining Power Capacity and Power Loss:
The system determines the power output by comparing the cell's ”Battery Capacity” with the first recorded discharge at start-up. In addition, BACS ensures that each battery reaches 100 % states of charge, making discharge tests comparable and consistent. With long-term data from BACSVIEWER, users can quickly identify and determine the lifetime power loss.
Autonomy time:
BACS calculates autonomy time by analysing UPS input, battery current, battery voltage, temperature and impedance. This calculation makes it easy for the user to get a clear estimate of how long the battery can keep the system running during operation.
Determination of Battery Capacity by Discharge Tests:
To accurately determine the available capacity, the user performs a discharge of the battery. BACS measures the capacity once per second throughout the discharge process. This allows tests to be carried out without causing damage to cells or batteries. In addition, BACS comprehensively monitors and analyses battery parameters. With the help of this analysis, users gain insights into battery performance, efficiency and life expectancy. Furthermore, BACS minimises the risk of system disturbances during online discharge tests.
Battery power
1. floating current - AC component (superimposed ripple current)
The ripple current, which consists of the AC component, occurs through the charger or load, such as inverters. It is superimposed on the DC flow current, leading to heat generation without contributing to the charging process. It is important to understand that this ripple current only creates heat and does not affect the charge level. When the ripple current reaches a high level at the same time as the DC current approaches zero, a discharge begins which rapidly deteriorates the condition of the lead-acid battery.
During the lifetime of the VRLA battery, the float current in its final stage doubles compared to a new battery. To deal with this scenario, BACS makes it possible to visually monitor the increase in float current. In addition, the system can trigger an alarm to provide an early warning signal in case of anomalies.
To reduce the risk of potential failures caused by this increased flow current, BACS offers the possibility to adjust the alarm levels for DC flow currents. This adjustment helps to avoid excessive water loss, deposition of active material and the risk of short circuits or overheating. In the worst case, these problems can lead to thermal breakdown, seriously affecting battery performance and durability.
2. maximum ripple current
In floating conditions, the operator limits the superimposed effective ripple current, especially at frequencies above 30 Hz, to ensure safety. To prevent potentially dangerous voltages or short circuits, precautionary measures are implemented, such as installing fast-blow fuses or current-limiting resistors in each sensing line.
In addition, BACS stands out among other BMS systems by using two high-voltage fuses in the sensing lines. To further enhance safety, BACS manufactures enclosures and components from fire-retardant materials and halogen-free cables. These material choices reduce the risk of damage from dangerous voltages. If necessary, BACS insulates the sensing lines with flame retardant and acid resistant materials.
If a blown fuse or sudden pulse voltages occur, the BACS automatically disconnects itself from the system. This action activates the alarm and provides an extra level of protection to minimise damage.
3. load sharing current
When multiple batteries are connected in parallel, BACS monitors current sensor values to ensure consistent performance. When discharging, the terminal voltage of each battery must be equal, provided that contacts have the same length and voltage drop. The batteries must also be of the same type, resistance and age to share the load current evenly.
A battery with low-performing cells shows a lower voltage-discharge profile than a healthy battery. When this battery is connected in parallel, it contributes less to the total load current. In such cases, the operation of the whole system can be negatively affected.
By comparing the differences between the maximum and minimum string current as a proportion of the total load current, the operator can identify performance differences. BACS enables these comparisons by displaying current values per string and adjusting thresholds for unbalanced values. When imbalances are detected, the operator can act quickly to optimise the system.
4. energy flow
BACS uses the latest CSHxxxF and CSHxxxD current sensors to measure energy flows with high precision. These sensors collect data that BACSVIEWER then converts into clear trend lines that visualise the battery or cell ageing process.
To assess the long-term health and performance of the battery, BACS monitors the self-discharge rate. By analysing the autonomy time of a specific battery or cell, the operator can identify increases in the self-discharge rate. If the autonomy time decreases faster than expected, this signals that the battery is ageing at an accelerated rate.
To determine the self-discharge rate, the operator cancels the maintenance charge when the battery is fully charged. BACS and SMARTLOGGER record and analyse the self-discharge over several days, while SMARTBATTERY presents the results.
The operator compares these values with the self-discharge rate of the battery when it was new. This analysis not only helps to understand the current status of the battery, but also enables predictions about future performance and lifetime. With these insights, the operator can optimise battery life and ensure reliable operation over time.
2. date of battery manufacture and commissioning
BACS, SMARTLOGGER and SMARTBATTERY record and archive battery manufacturing and commissioning data for up to 10 years. These systems ensure that the information remains available for future reference and analysis.
3. data access
Users always have easy and convenient access to the previously mentioned parameters. This accessibility not only facilitates comprehensive analyses to assess the residual value of the battery, but also supports the reuse or remanufacturing of the battery. In addition, it enables independent aggregators to use batteries in virtual power plants in the electricity grid.
BACS, SMARTLOGGER and SMARTBATTERY provide data in different formats, giving companies specialising in recycling a versatile information base. This supports companies in making informed decisions and optimising their recycling processes.
Furthermore, these technological developments and data availability open new opportunities in the recycling sector. The systems not only promote a better understanding of the health and performance status of batteries but also contribute to sustainability and efficient resource use.
4. long-term recording of data relating to storage and transport conditions
Manufacturers carefully collect data on the storage and transport conditions of batteries. This documentation is crucial to properly restructure batteries or identify any damage incurred during handling. By analysing this information, stakeholders gain a complete understanding of the battery life cycle and can take the necessary actions.
To ensure the process is carried out correctly, manufacturers follow quality control and safety guidelines at every stage - from examination and performance testing to packaging and transport. This way, they guarantee that the batteries reach their recipients in the best possible condition and avoid negative consequences from incorrect procedures.
GENEREX SMARTBATTERY and SMARTLOGGER continuously monitor and document the storage and transport conditions of each battery unit throughout its life cycle. This continuous data collection allows for precise control, improved quality control and maximum safety of the batteries.
5. availability of documentation
Manufacturers provide detailed documentation to clearly show the status and functionality of the battery. This information is crucial for actors involved in recycling, as it allows to evaluate battery ageing conditions and performance.
SMARTBATTERY, SMARTLOGGER and BACS play a central role by collecting and recording data from the early phases of the battery to its later stages. These technologies deliver comprehensive insights into battery performance and evolution, supporting an accurate and efficient recycling process.
By providing this documentation, schemes contribute to sustainable battery management practices. They help recycling operators make informed decisions and ensure that batteries are managed responsibly throughout their life cycle.
6. battery passport
By 1 January 2026, the EU requires every industrial and traction battery to have an electronic identification file, also called a ”battery passport.” This battery passport contains details such as the manufacturer's name, battery type, batch or serial number, date of manufacture, date of market launch and chemistry.
Manufacturers link the battery passport to information on the basic characteristics of each battery type, store this data in a non-volatile memory and make it available online. BACS, SMARTLOGGER and SMARTBATTERY already deliver all the data required for a battery passport in a permanent and easily accessible format.
The latest analysis shows that BACS, developed in Europe and North America, together with SMARTLOGGER and SMARTBATTERY, fulfil all requirements set by European and international regulatory bodies. These systems prepare the industry to meet future standards and support the sustainable development of battery management.
Contact us at
Here at Eurotech, we always endeavour to provide the best possible service at every contact.
Contact us for questions, a free consultation or to get a quote for uninterruptible power.
Mallslingan 20 A, 187 66 Täby
F.A.Q.
Frequently asked questions & answers
What does UPS mean?
UPS stands for "Uninterruptible Power Supply" and is a machine that protects electronic equipment from disturbances on the electricity grid and supplies them with power when there is a power cut.
What is UPS used for?
A UPS is used to ensure that there is power when there is a power cut or other types of interruption. This is so that you, as a user, do not lose your data or technical systems when the power goes out. A UPS is also used to protect electronic equipment from so-called power spikes. These power spikes can damage sensitive technical equipment.
Which UPS do I need?
Which UPS your business requires depends on 2 factors. Firstly, how many devices you need to secure power for, and where your equipment is located. You may need one or more UPSs for several different locations in the building or a larger UPS to handle more complex loads.
We can help you customise a UPS to your specific needs.
How many batteries does a UPS require?
The amount of batteries a UPS system requires depends on the UPS you have, but also the load your system has. There are minimum requirements for the number of batteries a UPS requires, but you can theoretically add as many as you like. However, more batteries do not mean that the system can handle a higher load, that limit is set by the UPS itself, but it can increase uptime.
How do I best look after my batteries?
First of all, buy good quality batteries. Batteries should be placed in an environment with an ambient temperature of between 22-22 degrees. Fit a BACS battery monitoring system to measure individual batteries so you get alerts when a battery goes bad and to perform individual charging. Alternatively, you should perform regular manual checks of the battery loop.
Where is Eurotech located?
In Täby Stockholm and in Alingsås.
Do you work throughout Sweden?
Yes, from Ystad in the south to Kiruna in the north.
What type of users do you have as customers?
Eurotech has been in the UPS market for more than 30 years and has a large proportion of Sweden's municipalities as customers, lift and property companies and a large part of the electrical installation industry. There are few industries that do not need uninterruptible power!
Do you perform maintenance on existing UPS systems?
Yes, we perform maintenance on existing UPS systems. We can sign contracts and perform regular maintenance depending on the scope that suits you. We perform service throughout Sweden and also have day service in case something unpredictable occurs.
My business does not fit into your industry categories.
We can customise solutions for all our customers. We look at the nature of your business and what type of UPS you need for a secure power supply.
Can not buying UPS be expensive?
Yes, definitely. In a power outage where there is no UPS or backup power, or the backup power takes a while to come on line, then many expensive production hours can be lost, as well as goods that depend on refrigeration, for example. A UPS is your parachute and bridge to uninterruptible power. A UPS is often a cheap investment, because not having one at all can be an expensive story.